• Do not let the balance tank run dry
  • Check and record levels on each shift
  • Use side stream filtration to keep the brine clean
  • Keep the pH between 7.5 and 8
  • Abnormally high pH levels can mean an ammonia leak
  • Keep the cooling floor freeze point between -5 and -10 F.
  • Keep the heating floor freeze point between 10 and 15 F.
  • Run pump once a month during the off season
  • Repair brine leaks immediately
  • Do a brine analysis every year